Select your region or visit global site

Support
Open navigation

Operation Modes

This chapter describes the behaviour of the Door Module in its specific operation modes, complementing the connection options presented in Quick Guides, and describing other connection options in full detail.

You can set the operation mode with the Door Module OPTIONS dip switches S1-S4.

The main principles of using OPTIONS dip switches are:

  • If S1 is enabled, the relay output K1 is calendar-controllable, otherwise not.
  • If S2 is enabled, the relay output K2 is calendar-controllable, otherwise not.
  • If S3 in enabled:
    • A valid key insertion to the cylinder connected to L1, activates the relay output K1 for 30 seconds.
    • A push button connected to IN1, activates the relay output K1 for 30 seconds.
  • If S4 in enabled:
    • A valid key insertion to the cylinder connected to L2, activates the relay output K2 for 30 seconds.
    • A push button connected to IN2, activates the relay output K2 for 30 seconds.

However, not all combinations are valid. The valid combinations are described in the following sections.

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article

Didn't find what you were looking for?

Submit a ticket