This section describes how to manually update bus device firmware.
Proceed as follows.
- Switch the Net Bridge switch to STANDBY.
- Switch the Net Bridge MODE switch to SETUP.
- Switch the Net Bridge switch to ON.
- Wait for one minute and see if the FUNC and RS-485 leds blink orange.
- If they do, there are bus devices that are undergoing a firmware update. Wait until the FUNC led is switched off and RS-485 led is constantly illuminated green.
- If they do not, continue from step 5.
- Switch the Net Bridge MODE switch to OPERATING.
- An internal test procedure is started.
Observe the green FUNC led for approximately one minute until the Net Bridge has saved the bus configuration. Check that:
- The green FUNC led blinks as many times as there are devices on the main bus.
- After a pause, the green FUNC led blinks as many times as there are devices on the reader buses.
- After a pause, the green FUNC led blinks as many times as there are lock cylinders connected on Door Modules.
The procedure ends when constant green FUNC, RS-485 STATUS, SYSTEM STATUS, and SERVER CONN. leds are illuminated.