Select your region or visit global site

Support
Open navigation

Troubleshooting

This section provides troubleshooting instructions for S10 Online System.

Table 1. Troubleshooting
LEDIndicationProblemSolution
Net Bridge in general
VCC, 5V, VDD, 5V BUSNot illuminatedNet Bridge hardware failure.Replace Net Bridge.
DC/POE/POE+Not illuminatedPowering issue.Check fuse F1. Check power supply.
Net Bridge in the OPERATING mode
RS-485 STATUSRedPower issue on a bus device.Check the connections for shortcuts and misconnections.
RS-485 STATUSBlinking red

The configuration detected on the bus differs from the one that was saved when last finalizing the bus device configuration. For example:

  • There are less or more devices on the bus, or slaves connected to a Door Module, than there should be.
  • The OPTIONS dip switch setup of a Door Module has been changed.
  • A Door Module programming state has been changed.
  • If you have changed the configuration on the bus on purpose, re-finalize the new bus configuration by running setup again, see Finalizing the Bus Device Configuration on Net Bridge.
  • If you have not changed the configuration on the bus, check the wiring to the bus devices, and slaves connected to the Door Module. The affected Door Module indicates the error by blinking red four times.
RS-485 STATUSOrangeLow voltage issue on a bus device.Too long cabling or too many devices on the bus. Double the power wiring or reduce the amount of devices on the bus. If PoE is used, use PoE+ or an external power supply instead.
RS-485 STATUSBlinks orangeFirmware update in progress.Do NOT power off the device. See Software and Firmware Updates.
RS-485 STATUSOffNo devices were found on the bus.Check the bus device connections. Finalize the Net Bridge configuration, see Finalizing the Bus Device Configuration on Net Bridge.
FUNC1Blinks redFinalizing the bus device configuration has failed.Finalize the bus device configuration by running the setup procedure, see Finalizing the Bus Device Configuration on Net Bridge.
FUNCBlinks red x 3Low voltage issue on a bus device.Too long cabling or too many devices on the bus. Double the power wiring or reduce the amount of devices on the bus. If PoE is used, use PoE+ or an external power supply instead.
FUNCBlinks red x 4Token not found.Insert token.
FUNCBlinks red x 5Operation mode not supported.Use a valid operation mode on the Door Module.
FUNCBlinks red x 10Door Module in formatted state.Change the Door Module to the factory state or program the Door Module as a lock.
FUNCBlinks red x 13Power issue.Check the connections for shortcuts and misconnections.
FUNCBlinks orangeFirmware update in progress.Do NOT power off the device. See Software and Firmware Updates.
FUNCRedConfiguration mismatch.
FUNCOrangeConfiguration error.Switch Net Bridge to the SETUP mode and back. The number of red blinks indicates the problem.
Net Bridge in the SETUP mode
FUNCBlinks orangeFirmware update in progress.Do NOT power off the device. See Software and Firmware Updates.
FUNCRedAddress error, duplicated addresses on bus devices.Change the address to a unique one.
RS-485 STATUSBlinks orangeFirmware update in progress.Do NOT power off the device. See Software and Firmware Updates.
Door Module
ERROR1Blinks red x 1Address error, duplicated addresses on bus devices.Change the address to a unique one.
ERRORBlinks red x 2Operation mode is not valid.Change the OPTIONS dip switches S1-S4 to establish a valid combination.
ERRORBlinks red x 3The Door Module has no time.Check that the Door Module has a connection to the Net Bridge.
ERRORBlinks red x 4

The configuration detected on the Door Module differs from the one that was saved when last finalizing the bus device configuration. For example:

  • There are less or more slaves connected to a Door Module, than there should be.
  • The OPTIONS dip switch setup of a Door Module has been changed.
  • A Door Module programming state has been changed.
  • If you have changed the configuration on the bus on purpose, re-finalize the new bus configuration by running setup again, see Finalizing the Bus Device Configuration on Net Bridge.
  • If you have not changed the configuration, check the wiring to the slaves connected to the Door Module.
LOW VOLTRedToo low voltage.Double the power supply wiring.
L1/L2OrangeLock cylinder is not programmed.Program the lock cylinder.
L1/L2RedInterference in the lock bus. Door Module ignores the Lock Cylinder.Contact iLOQ.
L3OrangeDoor Module in formatted state.Change the Door Module to the factory state or program the Door Module as a lock.
DEVICE, BRIDGE and SERVERBlinks green one by one from top to bottomThe Door Module firmware is being updated.Do NOT power off the device. See Software and Firmware Updates.
Key Reader
Topmost ledRedNo connection to Net Bridge.The hardware configuration has been changed and the setup has not been run. Run the setup. See Finalizing the Bus Device Configuration on Net Bridge.
Topmost ledOrangeNo connection to server, connection to Net Bridge ok.Check that the Net Bridge has established a server connection.
All three ledsIlluminated green, or illuminated green one by one from top to bottomThe Key Reader firmware is being updated.Do NOT power off the device. See Software and Firmware Updates.
RFID Reader
Top ledBlinks redConnection issue.
  • Check the wiring.

  • Ensure that the Net Bridge configuration has been finalized.

The table below lists troubleshooting instructions not related to any specific device LED.

Table 2. Non-LED-specific Troubleshooting
ProblemSolution

When finalizing the bus device configuration on Net Bridge, the FUNC led indicates less devices than connected.

A connected device appears in the device list of the Net Bridge on S10 Manager, but cannot be programmed remotely.Ensure that the user ID attached to the Net Bridge has all zones.
1 The LED blinks red on one-second intervals until a pause of a couple of seconds. The number of blinks in the sequence indicates the problem number.

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select atleast one of the reasons

Feedback sent

We appreciate your effort and will try to fix the article

Didn't find what you were looking for?

Submit a ticket